ProSoft Technology MVI56-103M User Manual
Page 130

Reference
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 130 of 152
ProSoft Technology, Inc.
February 22, 2013
TYPE 4: Time-tagged measurands with relative time
Bytes
Description
Spec
1
Value of 4
1
0x81
1
COT
1
Common address of ASDU
1
Function Type
1
Information number
4
SCL (short-circuit location (real))
7.2.6.20
2
RET (relative time)
7.2.6.15
2
FAN (fault number)
7.2.6.6
4
4-octet binary time
7.2.6.28
TYPE 5: Identification
Bytes
Description
Spec
1
Value of 5
1
0x81
1
COT
1
Common address of ASDU
1
Function Type
1
Information number
1
COL (compatibility level 2 or 3)
7.2.6.3
1
Char 1
7.2.6.2
1
Char 2
7.2.6.2
1
Char 3
7.2.6.2
1
Char 4
7.2.6.2
1
Char 5
7.2.6.2
1
Char 6
7.2.6.2
1
Char 7
7.2.6.2
1
Char 8
7.2.6.2
1
Manufacture byte
Free assignment
1
Manufacture byte
Free assignment
1
Manufacture byte
Free assignment
1
Manufacture byte
Free assignment