ProSoft Technology MVI56-103M User Manual

Page 105

Advertising
background image

MVI56-103M ♦ ControlLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 105 of 152

February 22, 2013

The following fields are used for each 10-word record in the command list:

Word Offset

Definitions

Description

0

Database Index

Address in module to associate with the command.

1

Session Index

Session index defined in the module to associate with the
command.

2

Sector Index

Sector index for session as defined in the module.

3

Data Type

ASDU data type associated with the command.

4

Function Code

Function Code for the command.

5

Point Index *

* Information

Number

Information object address for the point on which the
command operates.

6

Override Flag

Override flag for general command.

7

Override Value

Override value for general command.

8

Reserved

Reserved for future use.

9

Reserved

Reserved for future use.

The fields shown here are the same as those used in constructing the commands
in the Command List. For a detailed definition of the fields contained in this
block, refer to the Command List (page 39).

There is no response block built by the module to send back to the processor
after the 9901 block is processed. The commands are placed in the command
queue and issued at a high priority.

This block and block 9902 should be used when controlling double-point data
points in remote units using general commands. This provides complete control
of the slave devices under ladder logic control. Alternatively, the slaves can be
controlled by changing data in the database and having the data be transferred
using pre-

constructed commands in the user’s command list. Some points only

accept value of on for control (that is, LED reset or activate characteristic). For
these points, block 9901 and 9902 should only be utilized.