ProSoft Technology MVI56-103M User Manual

Page 35

Advertising
background image

MVI56-103M ♦ ControlLogix Platform

Configuring the MVI56-103M Module

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 35 of 152

February 22, 2013

2.3.4 Write Register Start

0 to 4999

The Write Register Start parameter specifies the start of the Write Data area in
module memory. Data in this area will be transferred in from the processor.

Note: Total user database memory space is limited to the first 5000 registers of module memory,
addresses 0 through 4999. Therefore, the practical limit for this parameter is 4999 minus the value

entered for Write Register Count, so that the Write Data Area does not try to extend above address

4999. Read Data and Write Data Areas must be configured to occupy separate address ranges in

module memory and should not be allowed to overlap.

2.3.5 Write Register Count

0 to 5000

The Write Register Count parameter specifies the size of the Write Data area of
module memory and the number of registers to transfer from the processor to
this memory area, up to a maximum value of 5000 words.

Note: Total Read Register Count and Write Register Count cannot exceed 5000 total registers.
Read Data and Write Data Areas must be configured to occupy separate address ranges in

module memory and should not be allowed to overlap.

2.3.6 Failure Flag Count

0 through 65535

This parameter specifies the number of successive transfer errors that must
occur before halting communication on the application port(s). If the parameter is
set to 0, the application port(s) will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.

2.3.7 Pass-Through Events

Y or N (N = Default)

This parameter specifies if event messages received on the Master ports will be
passed to the processor. If the parameter is set to N, event messages will not be
passed to the processor. If the parameter is set to Y, the module will pass all
events received to the processor using block identifier 9903.

Advertising