5.1.3 Hardware Specifications

Specification

Description

Backplane Current Load

800 mA @ 5 Vdc
3 mA @ 24 Vdc

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational
50 g non-operational
Vibration: 5 g from 10 Hz to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Debug/Configuration port (CFG)

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only

Application ports (PRT1 & PRT2)
Full hardware handshaking control, providing radio, modem and multi-drop support

Software configurable
communication parameters

Baud rate: 110 to 115,200 baud, depending on
protocol
RS-232, 485 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds

App Ports (P1, P2) (Serial
modules)

RJ45 (DB-9M with supplied cable)
RS-232 handshaking configurable
500V Optical isolation from backplane

Shipped with Unit

RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable

Cable Connections

The application ports on the MVI56-103M module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.

Note: When using RS-232 with radio modem applications, some radios or modems require
hardware handshaking (control and monitoring of modem signal lines). Enable this in the

configuration of the module by setting the UseCTS parameter to 1.