Configuring the MVI56-103M Module

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 34 of 152

ProSoft Technology, Inc.

February 22, 2013

2.3

[Backplane Configuration]

This section provides the module with a unique name, identifies the method of
failure for the communications for the module if the processor is not in RUN
mode, and describes how to initialize the module upon startup.

2.3.1 Module Name

0 to 80

characters

This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.

2.3.2 Read Register Start

0 to 4999

The Read Register Start parameter specifies the start of the Read Data area in
module memory. Data in this area will be transferred from the module to the
processor.

Note: Total user database memory space is limited to the first 5000 registers of module memory,
addresses 0 through 4999. Therefore, the practical limit for this parameter is 4999 minus the value

entered for Read Register Count, so that the Read Data Area does not try to extend above address

4999. Read Data and Write Data Areas must be configured to occupy separate address ranges in

module memory and should not be allowed to overlap.

2.3.3 Read Register Count

0 to 5000

The Read Register Count parameter specifies the size of the Read Data area of
module memory and the number of registers to transfer from this area to the
processor, up to a maximum of 5000 words.

Note: Total Read Register Count and Write Register Count cannot exceed 5000 total registers.

Read Data and Write Data Areas must be configured to occupy separate address ranges in
module memory and should not be allowed to overlap.