Configuring the MVI56-103M Module

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 30 of 152

ProSoft Technology, Inc.

February 22, 2013

1 128 128 25
1 144 128 26
205 100 133 51
205 100 133 52
END

This step should be repeated for each sector used by the application. The
module will only use the sectors configured in the previous step.

Step 5: Monitor Point Configuration (Monitor Direction)
After the slave receives a Class 1 or Class 2 request from the Master, it responds
with a message containing data. Each piece of equipment is normally configured
to respond with specific points when it is being polled with a Class 2 request.
During a Class 2 response, the slave may set a control bit (ACD) to inform the
Master that there are new events to be transmitted. Then, the Master will send a
Class 1 poll to read the events from the slave.

The IEC 60870-5-103 protocol states that the data is transferred between the
Master and slave using an ASDU (Application Service Data Unit) format. Each
format is given by:
 Type Identification
 Variable Structure Qualifier
 Cause Of Transmission
 Common Address of ASDU
 Function Type
 Information Number

Data…

Refer to the protection equipment specification for the following information about
each point:
 Type: Type of the message
 Function Type: Type of protection function
 Information Number: Point Identification
This information will identify each point in the MVI56-103M configuration file. The
user has to configure the points that will be updated in the MVI56-103M database
when a Class 2 or Class 1 response containing data is sent from the slave. Refer
to [IEC-103 Master Session x Sector y] section in the configuration file in order to
configure each point:

# ASDU Database Function Point
# Type Index Code Index
START
1 0 128 16
1 16 128 17
1 32 160 18
1 48 176 19
1 64 192 20
1 80 128 21
END

Where the user should enter:

ASDU Type: ASDU type for the point

Function Type: Function type for the point