ProSoft Technology MVI56-103M User Manual

Page 42

Advertising
background image

Configuring the MVI56-103M Module

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 42 of 152

ProSoft Technology, Inc.

February 22, 2013

2.6.7 Function Code

Code

Definition

128

Distance protection

160

Overcurrent protection

176

Transformer differential protection

192

Line Differential protection

255

Global function type

133

Meter Data for SIEMENS Devices

1

Reset Process

2

Class 2 Polls

x

User-defined

Note: The last item in the Function Code dropdown list is user-defined. If you select U

SER

D

EFINED

from the dropdown list, a text box will appear below the list. You may enter any function code in

this text box that will be accepted by the destination slave.

2.6.8 Point Index

The Point Index specifies the point address to be accessed in the remote slave
device.

Index Value

Description

1

Bit address with each point occupying 2 bits

2

Bit address with each point occupying 2 bits

3

Word address with each point occupying 4 words

4

Double-word address for the single float value

5

Byte address with each point occupying 12 bytes

9

Word address with each point occupying 9 words

2.6.9 Override Flag

0 or 1

Override Flag field is used for general commands to determine the value to be
written. If the override flag is clear (0), the value in the database will be utilized. If
the override flag is set (1), the value specified in the override value field will be
used.

2.6.10 Override Value

If the Override Flag is set to "Yes", you can use this setting to always force a
control parameter to a fixed value. Use Enable code C

ONDITIONAL

and the

database value for the command to determine when the value should be written.