ProSoft Technology MVI56-103M User Manual

Page 32

Advertising
background image

Configuring the MVI56-103M Module

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 32 of 152

ProSoft Technology, Inc.

February 22, 2013

# for the data in the command. The data type field determines
# the meaning of the index as follows:
# Type Description DB Index type
# ---- ----------------------------------- --------------------
# 6 Clock synchronization NA
# 7 General interrogataion NA
# 20 General Command Bit address
#
# Poll Interval field is utilized when the Enable Code is set to 1. This field
# determines the minimum number of seconds to wait between each
# execution of the command.
#
# Session Index represents the session index in the module to associate with
the
# command. This index is set when the session is read in from
# this file. The range of values for this field is 0 to 31.
#
# Sector Index represents the sector index for the specific session. The range
# of values for this field is 0 to 4.
#
# Data type file represents the ASDU type as follows:
# 0 = Special command
# 6 = Time synchronization
# 7 = General Interrogation
# 20 = General Command
#
# Function code
# Code Definition
# 128 Distance protection
# 160 Overcurrent protection
# 176 Transformer differential protection
# 192 Line Differential protection
# 205 Meter Data for SIEMENS Devices
# 255 Global function type
#
# Point Index field is used to specify the address in the remote slave device
# of the point to interact with.
#
# Override Flag field is used for general commands to determine the value
# to be written. If the override flag is clear (0), the value
# in the database will be utilized. If the override flag is set
(1),
# the value specified in the override value field will be used.
#
# Override Value field is utilized if the override flag is set. This can be
# used to always force a control parameter to a fixed value. The
# Enable code 2 and the database value for the command can be used
# to determine when the value should be written.
#
# Enable Database Poll Session Sector Data Func Point Ovrd Ovrd
# Code Index Interval Index Index Type Code Index Flag Val
START
1 0 0 0 0 6 255 0 0 0
1 10 0 0 0 7 255 0 0 0
END