Reference

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 120 of 152

ProSoft Technology, Inc.

February 22, 2013

[Section]/Item

Value

Range

Description

Sector Count:

1 to 5

This parameter sets the number of sectors
contained in this controlled device. This
version of the application supports 1 to 5
sectors for each session.

Data Link Address:

0 to 65535

This parameter uniquely defines the data link
address for this unit on the communication
channel.

Failure Delay:

0 to 2000

This parameter sets the minimum number of
seconds to delay before polling this session
when it is not online. This parameter is only
used in unbalanced mode.

Confirm Timeout:

0 to
4,294,967,296

This parameter sets the number of
milliseconds to wait for a confirm response
from the controlled device.

Retry Count:

0 to 255

This parameter sets the number of retries to
be performed on the controlled device when
a communication error occurs.

C1/C2 Poll Count Pend:

0 to 100

This parameter sets the maximum number of
Class 1 and Class 2 polls performed on this
session before trying the next session. This
parameter prevents a session from
monopolizing the communication port.

Class 1 Polls:

0 to 65535

This parameter sets the maximum number of
class one polls performed on this session
before switching to another session. This
parameter prevents a session from
monopolizing the communication port.

Class 1 Pend Delay:

0 to
4,294,967,296

This parameter sets the minimum number of
milliseconds to delay between Class 1 polls
for pending data.

Class 2 Pend Delay:

0 to
4,294,967,296

This parameter sets the minimum number of
milliseconds to delay between Class 2 polls
for pending data.

Class 1 Poll Delay:

0 to
4,294,967,296

This parameter sets the minimum number of
milliseconds to delay between each Class 1
poll.

Class 2 Poll Delay:

0 to
4,294,967,296

This parameter sets the minimum number of
milliseconds to delay between each Class 2
poll.

Response Timeout:

0 to
4,294,967,296

This parameter sets the maximum number of
milliseconds to wait for a confirmation from
the controlled station to a request from this
module.

[Section]/Item

Value

Range

Description

[IEC-103 MASTER
SESSION x SECTOR y]

This section sets the parameters for a
specific sector of a session.