ProSoft Technology MVI56-103M User Manual

Page 28

Advertising
background image

Configuring the MVI56-103M Module

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 28 of 152

ProSoft Technology, Inc.

February 22, 2013

Initially, the user should enter the MVI56-103M port number that will be
connected to the session (slave) using the "Communication Port" parameter.
Valid values are 0 or 1.

These parameters include the Data Link Address, which is the slave address that
identifies all protection equipment on the network. There should be a unique
number for each slave on the network. There are also certain parameters that
pertain to how the Class 1 and Class 2 polls will be used for data transfer.

You must enter the number of sectors for each session using the Sector Count
parameter. The module accepts up to 5 sectors per session.

[IEC-103 Master Session 0]
Communication Port : 0 #Index of COM port for session (0 or 1)
Sector Count : 5 #5 is max for this version of app
Data Link Address : 0 #Range is 0 to 65535 DL address of slave

Failure Delay : 3 #Min Sec to delay before poll of offline slave
#(0 to 2000 seconds)
Confirm Timeout : 20000 #0 to 4,294,967,295 msec to wait for DL confirm
Retry Count : 5 #0 to 255 retries for if no confirm
Response Timeout : 5000 #Timeout for confirm of req (0 to 4,294,967,295
msec)
C1/C2 Poll Count Pend: 6 #Class 1 or 2 polls before next slave tried (0-
65535)
Class 1 Polls : 10 #Max Class 1 polls to this session
Class 1 Pend delay : 1000 #Min mSec delay between call (0 to 4,294,967,295
msec)
Class 2 Pend delay : 1000 #Min mSec delay between call (0 to 4,294,967,295
msec)
Class 1 Poll delay : 1000 #Min mSec delay between call (0 to 4,294,967,295
msec)
Class 2 Poll delay : 1000 #Min mSec delay between call (0 to 4,294,967,295
msec)

This step should be repeated for each session to be used. For example, if the
user selected 8 sessions during Step 1, he or she should configure sessions 0 to
7:

[IEC-103 Master Session 0]
[IEC-103 Master Session 1]
[IEC-103 Master Session 2]
[IEC-103 Master Session 3]
[IEC-103 Master Session 4]
[IEC-103 Master Session 5]
[IEC-103 Master Session 6]
[IEC-103 Master Session 7]

Step 4: Sector (Data Set) Configuration
For each session (slave), you must configure one or more sectors (maximum of
5). A sector is a data set defined by the vendor. Each sector is identified by the
Common ASDU Address parameter in the [IEC-103 Master Session x Sector 0]
area in the configuration file. This area also contains some parameters that will
affect the module initialization procedure.

[IEC-103 Master Session 0 Sector 0]
Common ASDU Address : 0 #Range 0 to 255 Sector address