Note: Terminating resistors are generally not required on the RS-485 network, unless you are

experiencing communication problems that can be attributed to signal echoes or reflections. In

these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module
connector end of the RS-485 line may improve communication quality.

RS-485 and RS-422 Tip
If communication in the RS-422 or RS-485 mode does not work at first, despite
all attempts, try switching termination polarities. Some manufacturers interpret +
and -, or A and B, polarities differently.

DB9 to RJ45 Adaptor (Cable 14)