4 information numbers used in monitor direction – ProSoft Technology MVI56-103M User Manual

Page 124

Advertising
background image

Reference

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 124 of 152

ProSoft Technology, Inc.

February 22, 2013

5.8.4 Information Numbers Used in Monitor Direction

System functions

Inf

Description

GI

Type Fun

128

160

176

192

254

255

t(z)

l>>

l

T

l

L

GEN GLB

0

end of general interrogation

8

X

0

time synchronization

6

X

2

reset FCB

5

*

3

reset CU

5

*

4

start/restart

5

*

5

power on

5

*

* - According to main function

Status Indications

Inf

Description

GI

Type Fun

128

160

176

192

254

255

t(z)

l>>

l

T

l

L

GEN GLB

16

auto-recloser active

X

1

X

X

X

17

teleprotection active

X

1

X

X

18

protection active

X

1

X

X

X

X

19

LED reset

1

X

X

X

X

20

monitor direction blocked

X

1

X

X

X

X

21

test mode

X

1

X

X

X

X

22

local parameter setting

X

1

X

X

X

X

23

characteristic 1

X

1

X

24

characteristic 2

X

1

X

25

characteristic 3

X

1

X

26

characteristic 4

X

1

X

27

auxiliary input 1

X

1

X

X

X

X

28

auxiliary input 2

X

1

X

X

X

X

29

auxiliary input 3

X

1

X

X

X

X

30

auxiliary input 4

X

1

X

X

X

X

Advertising