MVI56-103M ♦ ControlLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 131 of 152

February 22, 2013

TYPE 6: Time synchronization

Bytes

Description

Spec

1

Value of 6

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

7

7-Octet binary time

7.2.6.29

TYPE 8: Termination of general interrogation

Bytes

Description

Spec

1

Value of 8

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

1

SCN (scan number 0 to 255)

7.2.6.21

TYPE 9: Measurands II

Bytes

Description

Spec

1

Value of 9

1

I = 1 to 9 for number of values

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

2

Current L

1

7.2.6.8

2

Current L

2

7.2.6.8

2

Current L

3

7.2.6.8

2

Voltage L

1-E

7.2.6.8

2

Voltage L

2-E

7.2.6.8

2

Voltage L

3-E

7.2.6.8

2

Active power P

7.2.6.8

2

Reactive power Q

7.2.6.8

2

Frequency f

7.2.6.8

Value of I determines number of parameters passed in the message with a range
of 1 to 9 but always starts with the L

1

value.