ProSoft Technology MVI56-103M User Manual
Page 132

Reference
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 132 of 152
ProSoft Technology, Inc.
February 22, 2013
5.8.7 Definition and Presentation of ASDUs in Control Direction
TYPE 6: Time synchronization
Bytes
Description
Spec
1
Value of 6
1
0x81
1
COT
1
Common address of ASDU
1
Function Type = GLB (255)
1
Information number
7
7-Octet binary time
7.2.6.29
TYPE 7: Initiation of general interrogation
Bytes
Description
Spec
1
Value of 7
1
0x81
1
COT
1
Common address of ASDU
1
Function Type = GLB (255)
1
Information number
1
SCN (scan number 0 to 255)
7.2.6.21
TYPE 20: General command
Bytes
Description
Spec
1
Value of 20
1
0x81
1
COT
1
Common address of ASDU
1
Function Type
1
Information number
1
DCO (1=Off, 2=On)
7.2.6.4
1
RII
7.2.6.19
RII is not to be processed within the protection equipment, but to be used as a
SIN of the return message.