Reference

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 132 of 152

ProSoft Technology, Inc.

February 22, 2013

5.8.7 Definition and Presentation of ASDUs in Control Direction

TYPE 6: Time synchronization

Bytes

Description

Spec

1

Value of 6

1

0x81

1

COT

1

Common address of ASDU

1

Function Type = GLB (255)

1

Information number

7

7-Octet binary time

7.2.6.29

TYPE 7: Initiation of general interrogation

Bytes

Description

Spec

1

Value of 7

1

0x81

1

COT

1

Common address of ASDU

1

Function Type = GLB (255)

1

Information number

1

SCN (scan number 0 to 255)

7.2.6.21

TYPE 20: General command

Bytes

Description

Spec

1

Value of 20

1

0x81

1

COT

1

Common address of ASDU

1

Function Type

1

Information number

1

DCO (1=Off, 2=On)

7.2.6.4

1

RII

7.2.6.19

RII is not to be processed within the protection equipment, but to be used as a
SIN of the return message.