Reference

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 114 of 152

ProSoft Technology, Inc.

February 22, 2013

5.6

MVI56-103M Status Data Area

This section contains a listing of the data contained in the MVI56-103M status
data object, configuration error word and module error codes.

5.6.1 MVI56-IEC 60870-5-103 Master Communication Module

Error/Status Data Format

Status
Table
Word

Parameter

Description

0

Scan Count

This status value contains a counter incremented on each scan of the
module's main loop.

1 to 2

Product Name

This two-word data area contains the text values representing the
product name. These words contain the text "I3M5" for the MVI56
platform.

3 to 4

Revision

This two-word data area contains the text values for the revision
number.

5 to 6

Op Sys #

This two-word data area contains the text values for the operating
system number.

7 to 8

Run Number

This two-word data area contains the text values for the run number.

9

Read Blk Cnt

This word contains the total number of block read operations
successfully executed.

10

Write Blk Cnt

This word contains the total number of block write operations
successfully executed.

11

Parse Blk Cnt

This word contains the total number of write blocks successfully
parsed.

12

Error Blk Cnt

This word contains the total number of block transfer errors.

13

Event Msg Cnt This word contains the number of event messages waiting to send to

the processor.

14

Event Msg
Overflow

This word contains a value of 0 if the event message buffer has not
overflowed. If the event buffer overflows, this word will be set to a
value of 1.

15

Session Count This word contains the number of session configured in the module.

16

Current Cmd

This word contains the index of the current command being executed
in the command list.

17

Cmd Busy Flag This word is set to zero if no command is currently being executed and

waiting on a response. If the word is set to 1, a command is currently
executing.

18

Cmd Count

This word contains the count of the number of commands configured
for the module.

19

Cmd Delay

This word contains the command delay counter preset. There is a
fixed delay between each command to permit the module to perform
class polls on controlled stations.

20

Cmd Queue

This word is set to zero if the command executing is from the
command list. If the executing command is from the command queue,
the word will be set to 1.

Advertising