MVI56-103M ♦ ControlLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 121 of 152

February 22, 2013

[Section]/Item

Value

Range

Description

Common ASDU Address:

0 to 255

This parameter sets the common ASDU
address to association with this sector of the
specified session. This parameter is usually
set the same as the Data Link Address
when only one sector is utilized.

Online Time Sync:

Yes or No This parameter specifies if the sector in the

controlled device will be sent a time
synchronization command when the unit is
first recognized as being online. This should
only be utilized for devices that do not send
an EOI message after initializing.

Online General Int:

Yes or No This parameter specifies if the sector in the

controlled device will be sent a general
interrogation command when the unit is first
recognized as being online. This should only
be utilized for devices that do not send an
EOI message after initializing.

EOI Time Sync:

Yes or No This parameter specifies if the sector in the

controlled device will be sent a time
synchronization command after this module
received an EOI message from the
controlled unit.

EOI General Int:

Y or N

This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module
received an EOI message from the
controlled unit.