5.8.2 List of Cause of Transmission Codes

In Monitor Direction

COT

Description

1

spontaneous

2

cyclic

3

reset frame count bit (FCB)

4

reset communication unit (CU)

5

start/restart

6

power on

7

test mode

8

time synchronization

9

general interrogation

10

termination of general interrogation

11

local operation

12

remote operation

20

positive ack of command

21

negative ack of command

31

transmission of disturbance data

40

positive ack of generic write command

41

negative ack of generic write command

42

valid data response to generic read command

43

invalid data response to generic read command

44

generic write confirmation

In Control Direction

COT

Description

8

time synchronization

9

initiation of general interrogation

20

general command

31

transmission of disturbance data

40

generic write command

42

generic read command

5.8.3 List of Function Types

Fun

Description

Symbol

128

Distance protection

t(z)

160

Overcurrent protection

l>>

176

Transformer differential protection

l

T

192

Line differential protection

lL

254

Generic function type

GEN

255

Global function type

GLB