ProSoft Technology MVI56-103M User Manual

Page 109

Advertising
background image

MVI56-103M ♦ ControlLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 109 of 152

February 22, 2013

5.4.4 Read Command Error List Block (9950)

Block 9950 identification code requests the Command List Error Table from the
module for the 1000 user-configurable commands. The format for the block is
shown below:

Word Offset
in Block

Data Field(s)

Description

0

Block ID

This field contains the value of 9950 identifying the block type
to the module.

1

Number of
Commands to
report

This field contains the number of commands to report in the
response message. The value has a range of 1 to 200.

2

Start Index of First
Command

This parameter sets the index in the command list where to
start. The first command in the list has a value of 0. The last
index in the list has a value of MaxCommands -1.

3 to 247

Spare

Not Used

The module will respond to a valid request with a block containing the requested
error information. The following table describes the format of this block.

Word Offset
in Block

Data Field(s)

Description

0

Reserved

Reserved (0)

1

Block ID

This is the next block requested by the module.

2

Number of
Commands
reported

This field contains the number of commands contained in the
block that must be processed by the PLC. This field will have
a value of 1 to 200.

3

Start Index of First
Command

This field contains the index in the command list for the first
value in the file. This field will have a value of 0 to
MaxCommands-1.

4 to 203

Command List
Errors

Each word of this area contains the last error value recorded
for the command. The command index of the first value
(offset 4) is specified in word 3 of the block. The number of
valid command errors in the block is set in word 2 of the
block. Refer to the command error list to interpret the error
codes reported.

204 to 248

Spare

Not Used

249

Block ID

This field contains the value of 9950 identifying the block type
to the PLC.

Advertising