ProSoft Technology MVI56-103M User Manual

Page 70

Advertising
background image

Diagnostics and Troubleshooting

MVI56-103M ♦ ControlLogix Platform

User Manual

IEC 60870-5-103 Master Communication Module

Page 70 of 152

ProSoft Technology, Inc.

February 22, 2013

1 Verify that the null modem cable is connected properly between your

computer’s serial port and the module. A regular serial cable will not work.

2 Verify that RSLinx is not controlling the COM port. Refer to Disabling the

RSLinx Driver for the Com Port on the PC.

3 Verify that your communication software is using the correct settings for baud

rate, parity and handshaking.

4 On computers with more than one serial port, verify that your communication

program is connected to the same port that is connected to the module.

If you are still not able to establish a connection, you can contact ProSoft
Technology Technical Support for further assistance.

4.1.4 Main Menu

When you first connect to the module from your computer, your terminal screen
will be blank. To activate the main menu, press the [?]

key on your computer’s

keyboard. If the module is connected properly, the following menu will appear.

Caution: Some of the commands available to you from this menu are designed for advanced

debugging and system testing only, and can cause the module to stop communicating with the
processor or with other devices, resulting in potential data loss or other failures. Only use these

commands if you are specifically directed to do so by ProSoft Technology Technical Support staff.

Some of these command keys are not listed on the menu, but are active nevertheless. Please be

careful when pressing keys so that you do not accidentally execute an unwanted command.

Viewing Block Transfer Statistics

Press [B]

from the Main menu to view the Block Transfer Statistics screen.

Use this command to display the configuration and statistics of the backplane
data transfer operations between the module and the processor. The information
on this screen can help determine if there are communication problems between
the processor and the module.

Tip: To determine the number of blocks transferred each second, mark the numbers displayed at a
specific time. Then some seconds later activate the command again. Subtract the previous

numbers from the current numbers and divide by the quantity of seconds passed between the two

readings.

Advertising