2.8

[IEC-103 Master Session x Sector y]

This section defines Sector z, which belongs to Session y. The Sector Count
parameter (page 43) in the [IEC-870-5-103 Master Session y] section specifies
the number of sectors for the session.

Each sector has a corresponding [IEC-103 Master Session y Sector z] section,
where y represents the session index and z represents the sector index.

The sectors are referenced by a zero-based index value. For example, if Session
0 is configured for four sectors, the configuration file should contain sections for
Sectors 0 to 3 (that is, [IEC-103 Master Session 0 Sector 0] to [IEC-103 Master
Session 0 Sector 3]
).

2.8.1 Common ASDU Address

0 to 255

This parameter sets the common ASDU address to association with this sector of
the specified session. This parameter is usually set the same as the Data Link
Address
when only one sector is used.

2.8.2 Online Time Sync

Yes or No

This parameter specifies if the sector in the controlled device will be sent a time
synchronization command when the unit is first recognized as being online. This
should only be used for devices that do not send an EOI message after
initializing.

2.8.3 Online General Int

Yes or No

This parameter specifies if the sector in the controlled device will be sent a
general interrogation command when the unit is first recognized as being online.
This should only be used for devices that do not send an EOI message after
initializing.

2.8.4 EOI Time Sync

Yes or No

This parameter specifies if the sector in the controlled device will be sent a time
synchronization command after this module received an EOI message from the
controlled unit.

2.8.5 EOI General Int

Yes or No

This parameter specifies if the sector in the controlled device will be sent a
general interrogation command after this module received an EOI message from
the controlled unit.