Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference

110 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Autonomous Message

TP-SSU 03-10-24 10:45:15

A 1179 REPT EVT

“GPS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-45-15:\"GPS LOCATION

HAS CHANGED,MANUAL\””

;

Setting the Input Frequency

Use the ED-SYNC command to provision the input PRS frequency.

ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;

This command has a default access level of ADMIN.

Sample Command

ED-SYNC::PRS:TS1000::FRMTYPE=5M;

Autonomous Message

TP-SSU 03-10-24 10:46:01

A 1179 REPT EVT

“PRS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-46-01:\"INPUT

FRAMING TYPE HAS CHANGED,5M\””

;

Setting the Input Frame Type

Use the ED-SYNC command to provision the type of framing present on the input
signal.

ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;

If you provision the TimeProvider to the Subtending mode (see

Setting the System

Mode

, on page 105), then the input frame type is automatically set to Composite

Clock type signals. You can set the FRMTYPE to CC, JCC, or JCC4 when the
TimeProvider is in the Subtending mode.

When using E1 signals in the SSU mode, you can enter either CAS or CCS in the
FRMTYPE keyword. The TimeProvider accepts both CCS and CAS inputs without a
fault (if the input is fault-free).

This command has a default access level of ADMIN.

<aid>

<keyword>

<value>

Description

Default value

PRS

FRMTYPE

1.544 M | 2M | 5M |
6.312 M | 10M

Provisions the input
frequency of the PRS input

2M