Alarm conditions and defaults, Table 4-3 – Symmetricom EDGE CLOCK 1000 User Manual

Page 127

Advertising
background image

097-58001-02 Revision G – April 2008

TimeProvider User’s Guide 127

Chapter 4 Provisioning the TimeProvider

Provisioning Alarms

Table 4-3. Alarm Conditions and Defaults

Alarm ID

Description of Alarm

Condition

Possible

Alarm

Levels

Error

Delay

Default

Error

Delay

Editable?

Default Level

SSU

Mode

SUB

Mode

<aid> = SYS

PWRA

Loss of A power

MN | MJ |
CR

IMMED

No

MJ

MJ

PWRB

Loss of B power

MN | MJ |
CR

IMMED

No

MJ

MJ

EXPFAIL

Connection to the
Expansion Panel is lost

NR | NA |
MN | MJ |
CR

IMMED

No

MJ

MJ

EXTALM

External alarm
generated by external
equipment

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

<aid> = IMC

IOC1COMM

Comm alarm with IOC
1

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

IOC2COMM

Comm alarm with IOC
2

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

<aid> = IOC

IOC1COMM

Comm alarm from IMC
module to IOC1 module

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

IOC2COMM

Comm alarm from IMC
module to IOC2 module

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

IOC1TO2
COMM

Comm alarm from
IOC1 to IOC2

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

IOC2TO1
COMM

Comm alarm from
IOC2 to IOC1

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

IOCFAIL

Summary alarm of IOC
failures; for example,
calibration was unsuc-
cessful

MN | MJ |
CR

IMMED

No

MJ

MJ