TimeProvider User’s Guide 129

Chapter 4 Provisioning the TimeProvider

Provisioning Alarms

<aid> = INP1 or INP2

INPDISQ

Specified input has
been disqualified or
qualified as a possible
system reference.

MN | MJ |
CR

FLT
DELAY

Yes

MN

MN

INPAIS

The specified input is
receiving an Alarm

Indication Signal.

1

MN | MJ |
CR

IMMED

No

MN

MN

INPLOS

The specified input has

Loss of Signal.

1

MN | MJ |
CR

IMMED

No

MN

MN

INPOOF

The specified input is
receiving an Out of

Frame signal.

1

MN | MJ |
CR

IMMED

No

MN

MN

INPFRQ

Specified input port’s
calculated received
frequency exceeds the
pull-in range of the
LO.This alarm condition
disqualifies the input as

a possible reference.

2

NR | NA |
MN | MJ |
CR

IMMED

No

MN

NR

INPPHASE

Specified input port’s
phase measurement
exceeds usable value.

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

INPQL

The received SSM is of
lesser quality than the
provisioned QLEVEL for
a specified input. This
alarm occurs when you
provision the input’s
QLEVEL below the
quality level of the LO.

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

EXDSC

Input has had excessive
discontinuities, indicated
by more than 3 signal
faults (OOF, BPV, CRC,
or AIS) within a 5-minute
window. The alarm
clears when the 5-
minute window contains
less than 3 signal faults.

NR | NA |
MN | MJ |
CR

IMMED

No

MN

MN

Table 4-3. Alarm Conditions and Defaults (Continued)

Alarm ID

Description of Alarm

Condition

Possible

Alarm

Levels

Error

Delay

Default

Error

Delay

Editable?

Default Level

SSU

Mode

SUB

Mode