TimeProvider User’s Guide 177

Chapter 6 Maintaining and Troubleshooting the TimeProvider

Troubleshooting the TimeProvider

EXTALM
1

External alarm 1 – monitors
alarms generated by external
equipment.

EQPT

NSA

MJ

MJ

MJ

EXTALM
2

External alarm 2 – monitors
alarms generated by external
equipment.

EQPT

NSA

CR

CR

CR

EXPN
EQPT

Output Expansion Panel has
been removed or installed

EQPT

NSA

MJ

MJ

MJ

PWRA

Loss of power on PWRA.

EQPT

NSA

MJ

MJ

MJ

PWRB

Loss of power on PWRB.

EQPT

NSA

MJ

MJ

MJ

IOC1
EQPT

The IOC has been physically
inserted or removed from the
shelf.

EQPT

NSA

MJ

MJ

MJ

IOC2
EQPT

The IOC has been physically
inserted or removed from the
shelf.

EQPT

NSA

MJ

MJ

MJ

AID = IMC

IOC1
COMM

Communication alarm with
IOC1.

EQPT

NSA

MN

MN

MN

IOC2
COMM

Communication alarm with IOC2.

EQPT

NSA

MN

MN

MN

IMCFAIL

Summary alarm of IMC BIST faults.

EQPT

SA

MJ

MJ

MJ

AID = IOC1

IOC1
COMM

Communication alarm with IMC
and IOC1.

EQPT

NSA

MN

MN

MN

IOC1TO2
COMM

Communication alarm from
IOC1 to IOC2.

EQPT

NSA

MN

MN

MN

IOCFAIL

Summary alarm for IOC
hardware failures not specified
in other alarms.

EQPT

SA

MJ

MN

MJ

BTBCK
UP

All BesTime backup sources
are unusable to the BesTime
engine.

EQPT

NSA

NA

NA

NA

Table 6-7. Alarm Codes (Continued)