Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference

114 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Sample Command

ED-SYNC::PRS:TS1000::PRIORITY=2;

ED-SYNC::INP1:TS1000::PRIORITY=2;

ED-SYNC::INP2:TS1000::PRIORITY=2;

These commands set the PRIORITY for each input to the same value; if you also
provision the QLEVEL to the same value, then you set up a non-revertive switching
strategy.

Autonomous Message

TP-SSU 03-10-24 10:56:00

A 1184 REPT EVT

“PRS,EQPT:NA,PRIORITY,NSA,03-10-24 10-56-00:\"PRIORITY

HAS CHANGED,2\””

;

Manually Selecting the Reference

Use the ED-SYNC command to manually select the reference. To select the
reference, you must first set the REFMODE keyword to FORCED, as described in

Controlling Automatic Reference Switching

, on page 111.

ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;

This command has a default access level of ADMIN.

Sample Command

ED-SYNC::SYS:TS1000::INPREF=PRS;

This command forces the signal on the PRS input to be the reference signal. The
REFMODE keyword must be set to FORCED for this command to take effect.

Autonomous Message

TP-SSU 03-10-24 10:58:30

A 1185 REPT EVT

“SYS,EQPT:NA,INPREF,NSA,03-10-24 10-58-30:\”SYSTEM

REFERENCE INPUT HAS CHANGED, PRS\””

;

<aid>

<keyword>

<value>

Description

Default value

SYS

INPREF

GPS | PRS | INP1 |
INP2

Sets the specified
input to be the
system reference

PRS