Chapter 4 Provisioning the TimeProvider
Provisioning the Outputs

118 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Autonomous Message

TP-SSU 03-10-24 11:09:12

A 1189 REPT EVT

“GPS,EQPT:THRCHG,THRCHG,03-04-05 15-17-57,,,,:\”PM

THRESHOLD HAS CHANGED,MASK,GPS-R \””

;

Setting Alarm Levels for Performance Monitoring Faults
Once you set a threshold for performance monitoring faults, you can set the alarm
level to indicate that a fault has occurred. Use the SET-ATTR command to set the
alarm level.

SET-ATTR:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;

This command has a default access level of ADMIN.

Sample Command

SET-ATTR::GPS:TS1000::MTIE=MJ;

This command sets the GPS input to report a Major alarm when the MTIE
performance threshold is exceeded.

Autonomous Message

TP-SSU 03-05-15 09:59:09

A 1189 REPT EVT

“GPS,EQPT:ALMCHG,ALMCHG,03-04-05 15-17-57,,,,:\”ALARM

PARAMETER HAS CHANGED,GPS,MJ\””

;

Provisioning the Outputs

This section describes the commands you use to provision the outputs of the
TimeProvider. You provision outputs in groups of 8 (or 16 if the Expansion Panel is
used) channels: each group corresponds to the location (A through D) of the Output
module in the main shelf or Expansion Panel.

<aid>

<keyword>

<value>

Description

GPS, PRS,
INP1, INP2

MTIE

NR | NA | MN | MJ | CR

The alarm level when the specified
input has exceeded at least one of
the MTIE thresholds

FFOFF

NR | NA | MN | MJ | CR

The alarm level when the specified
input has exceeded the FFOFF
threshold