Led conditions for the imc and imc/tpiu – Symmetricom EDGE CLOCK 1000 User Manual

Page 147

Advertising
background image

097-58001-02 Revision G – April 2008

TimeProvider User’s Guide 147

Chapter 5 Testing the TimeProvider

Verifying Normal Operation

Table 5-2

shows the condition of the LED indicators on the front panel of the IMC

under normal operating conditions.

Holdover

Off

Tracking at least one input

PRS

Q LED Green, A LED Green
Q LED Green, A LED Off
Q LED Red, A LED Off

Enabled, qualified, and active
Enabled, qualified, and not active
Enabled and not qualified

Input 1

Q LED Green, A LED Green
Q LED Green, A LED Off
Q LED Red, A LED Off

Enabled, qualified, and active
Enabled, qualified, and not active
Enabled and not qualified

Input 2

Q LED Green, A LED Green
Q LED Green, A LED Off
Q LED Red, A LED Off

Enabled, qualified, and active
Enabled, qualified, and not active
Enabled and not qualified

GPS

Off
Green
Amber
Red

1 PPS signal is not present
1 PPS signal is active
Bridging mode fault
Loss of 1 PPS signal, TPIU fault, or
antenna fault

Table 5-2. LED Conditions for the IMC and IMC/TPIU

LED Name

Condition

Description

Power

Green

Power is On

Fail

Off

No failure

Alarm

Off

No alarm

Critical

Off

No Critical alarms

Major

Off

No Major alarms

Minor

Off

No Minor alarms

ACO

Off

Alarm cutoff disabled

Table 5-1. LED Conditions for the IOC (Continued)

LED Name

Condition

Description

Advertising
This manual is related to the following products: