Symmetricom EDGE CLOCK 1000 User Manual

Page 181

Advertising
background image

097-58001-02 Revision G – April 2008

TimeProvider User’s Guide 181

Chapter 6 Maintaining and Troubleshooting the TimeProvider

Troubleshooting the TimeProvider

INPFRQ

The specified input port’s
calculated received frequency
exceeds the pull-in range of the
LO. This alarm disqualifies an
input as a system reference.
Once set, this alarm clears
when the input frequency is
within the defined pull-in range
limits.

T1

NSA

MN

MN

MN

INP
PHASE

The specified input port has an
excessive phase measurement
that disqualifies it from being
used.

T1

NSA

MN

MN

MN

EXDSC

The specified input has had
excessive discontinuities,
indicated by more than 3 signal
faults of the same type within a
5-minute window. The alarm
clears when the window
contains less than 3 alarms of
the same type.

T1

NSA

MN

MN

MN

FFOFF

The specified input port has
exceeded the Fractional
Frequency Offset threshold.

T1

NSA

MN

MN

MN

MTIE

The specified input port has
exceeded at least 1 of the MTIE
alarm thresholds.

T1

NSA

MN

MN

MN

AID = INP1 or INP2

INPDISQ

The specified input port has
been disqualified as a possible
system reference. The fault
condition must be continuously
present for the FLTDELAY
period before disqualifying the
input as a possible reference.
Once set, this alarm clears
when the input is fault-free for
the CLRDELAY period.

T1

NSA

MN

MN

MN

Table 6-7. Alarm Codes (Continued)

Event ID

Description

AID

TYPE

Service

Affecting

Alarm Level

SSU

Mode

PRR

Mode

SUB

Mode