Displaying alarm status – Symmetricom EDGE CLOCK 1000 User Manual

Page 134

Advertising
background image

Chapter 4 Provisioning the TimeProvider
Provisioning Alarms

134 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Normal Response

TP-SSU 03-10-24 11:22:11

M

TS1000 COMPLD

"SYS,EQPT:MJ,PWRA,NSA,03-10-24 11-22-11:\"POWER A FAILED\""

"SYS,EQPT:MJ,EXPFAIL,SA,03-10-24 11-22-11:\"EXPANSION CONNECTIVITY FAILED\""

"IOC2,EQPT:MJ,CLKFREE,SA,03-10-24 11-25-15:\"CLOCK ENTERED FREE-RUN MODE\""

"INP1,T1:MN,INPLOS,NSA,03-10-24 11-25-16:\"LOS FAULT\""

"INP2,T1:MN,INPDISQ,NSA,03-10-24 11-25-17:\"INPUT DISQUALIFIED AS POSSIBLE

REFERENCE\""

"INP2,T1:MN,INPLOS,NSA,03-10-24 11-25-17:\"LOS FAULT\""

;

Displaying Alarm Status

The RTRV-COND command displays information about the current summary alarm
status of components within the TimeProvider. The active IOC reports alarms for the
Input, Output, and Expansion Panel.

RTRV-COND:[<tid>]:<aid>:[<ctag>];

This command always has an access level of USER.

Normal Response Format

<cr><lf><lf>

^^^sid^date^time<cr><lf>

M ^ctag^COMPLD<cr><lf>

^^^”SYS:<pwra>,<pwrb>,<expstatus>,<extfault>,<ioc1eqpt>,

<ioc2eqpt>,<sysqlevel>,<lastdat>,<lasttim>”<cr><lf>

^^^”IMC:<ioc1comm>,<ioc2comm>”<cr><lf>

[^^^”IOC1:<iocstatus>,<ioccomm>,<imccomm>”<cr><lf>]

[^^^”IOC2:<iocstatus>,<ioccomm>,<imccomm>”<cr><lf>]

^^^”GPS:<gpsstatus>”<cr><lf>

^^^”PRS:<prsstatus>”<cr><lf>

^^^”INP1:<inpstatus>”<cr><lf>

^^^”INP2:<inpstatus>”<cr><lf>

^^^”OUTA:<outstatus>”<cr><lf>

^^^”OUTB:<outstatus>”<cr><lf>

^^^”OUTC:<outstatus>”<cr><lf>

^^^”OUTD:<outstatus>”<cr><lf>

;

<aid>

Description

ALL (or null)

Access Identifiers

Advertising