Chapter 5 Testing the TimeProvider
Testing Alarm Conditions

148 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Testing Alarm Conditions

Testing the IOC Operating Modes

Warm-up Mode
The IOC enters and remains in the Warm-up mode for approximately 30 minutes
after you apply power to the shelf, or when you install the IOC into the shelf. The
following actions occur when an IOC enters the Warm-up mode:

The Power LED on the IOC flashes green

An event is generated and stored in the event log

To verify that an IOC is in warm-up mode:

1. Apply an appropriate signal to the INP1, INP2, and/or PRS inputs.

2. Visually inspect the Power LED on the appropriate IOC. The LED is flashing

green in the Warm-up mode.

3. Type

RTRV-ALM::IOC1;

(or

RTRV-ALM::IOC2;

). The TimeProvider responds

with a complied message indicating that the designated IOC is in alarm.

Locked Mode
The IOC enters and remains in the locked mode after it has completed the warm-up
cycle. The following actions occur when an IOC enters the Locked mode:

The Power LED on the IOC is green

An event is generated and stored in the event log

To verify that an IOC is in locked mode:

1. Visually inspect the Power LED on the appropriate IOC. The LED is continually

green when the IOC is tracking at least one input.

2. Type

RTRV-LOG::IOC1:::EVT;

(or

RTRV-LOG::IOC2:::EVT;

). The

TimeProvider responds with a list of events related to the specified IOC. Look for
the entry with the text “Clock entered lock mode.”