Start-up Check List

108

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual

p/n: 029-0021-68-0

Note: If the system is equipped with an ADT or MDT II, move the selector to
TANK B position and repeat steps 8 through 10 for Tank B.

12.

After foam pump operation has been checked with both foam tanks exit
simulated flow mode by selecting the FLOW display and depressing
both up

Ï and down Ð buttons simultaneously.

13.

Drain water from foam tanks and concentrate lines and return the
bypass valve to the INJECT position.

14.

Verify operation of and calibrate flow sensor(s) as required using flow
sensor calibration procedures in the user calibration section.

This completes the Hale FoamLogix system operation checks that can be
accomplished at the system installer facility. Foam pump feedback calibra-
tion along with setting of user specified default simulated flow and concen-
trate injection rates should be accomplished upon delivery to the end user
using actual end user specified foam concentrates and default values.