Entering passwords, Figure 4-3: password sequence, Caution – Hale FoamLogix 6.5 User Manual

Page 112

Advertising
background image

Setup and Calibration

112

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual

p/n: 029-0021-68-0

The system allows easy checking of component calibration to assure accu-
rate operation. The calibration process verifies the calibration process and
allows adjustments to the flow sensor and feedback sensor display read-
ings, to allow for variations in apparatus piping configurations and end user
selected foam concentrate.

Default values for simulated flow and the foam concentrate injection rate
may be set to end user specifications while in the calibration mode.

Note: The Hale FoamLogix system is calibrated at the factory to U.S. measure-
ment (GPM, PSI, GALLONS, etc.) units. The system may be set to Metric units.
See heading “English to Metric Units” on page 120. However, the same unit of
measurement must be used throughout the calibration process to ensure proper
proportioning by the system.

Recalibration of the system may be required ONLY after major repairs or
component changes are made to the Hale FoamLogix foam system. Differ-
ent viscosity foam concentrates may also require recalibration.

CAUTION !

WATER IS USED AT THE SYSTEM INSTALLER FACILITY TO VERIFY LOW
TANK LEVEL SENSOR OPERATION AND FOAM PUMP OPERATION, AS THE
END USER SPECIFIED FOAM CONCENTRATES MAY NOT BE READILY
AVAILABLE.

DO NOT PUMP WATER WITH THE HALE FOAMLOGIX FOAM PUMP FOR
MORE THAN ONE (1) MINUTE. DO NOT ATTEMPT TO CALIBRATE FOAM
PUMP FEEDBACK SENSOR WITH OTHER THAN END USER SPECIFIED
FOAM CONCENTRATE.

MAKE SURE THE BYPASS VALVE IS IN THE “BYPASS” POSITION WHEN
PUMPING WATER WITH THE FOAM PUMP.

Entering Passwords

Entering a password is accom-
plished using the up and down
arrow buttons on the display unit.

1. To enter passwords, press and hold

the DISPLAY button. The display
briefly shows PASS, then clears.

2. While continuing to hold the display

button press the or buttons sequentially to enter the password. (See
Figure 4-3: “Password Sequence.”)

Mode

Password Sequence

ENTER User
Calibration

RESTORE Factory
Default Values

Figure 4-3: Password Sequence