Foam concentrate injection rate, Foam pump feedback calibration, 2 user calibration - continued – Hale FoamLogix 6.5 User Manual

Page 116

Advertising
background image

Setup and Calibration

116

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual

p/n: 029-0021-68-0

2. Adjust the setting to the required rate by pressing the or buttons (e.g.,

S 150).

Foam Concentrate Injection Rate

When the Hale FoamLogix system is powered ON, the foam concentrate
injection rate stored in memory is the default setting. The user specific
default concentrate injection rate is adjusted in the calibration mode.

1. Press the

i

button.

The display shows the
current default concen-
trate injection rate
stored in memory for the
selected foam concen-
trate tank. (See Figure
4-8: “Foam Concentrate
Injection Rate Default
Value, Tank “A”
Shown.”)

2. If the factory default val-

ues have not been
changed the display
shows PA 0.5. for Tank
“A” or PB 1.0 for Tank “B”.

3. Use the or buttons to set the user specified default concentrate injection

rate. (See Figure 4-8: “Foam Concentrate Injection Rate Default Value, Tank
“A” Shown” on page 116.)

Foam Pump Feedback Calibration

IMPORTANT !

FOAM PUMP FEEDBACK IS CALIBRATED AFTER INSTALLATION TO VERIFY
VALUES WITH THE ACTUAL FOAM CONCENTRATE(S) BEING USED. ONLY
CALIBRATE USING ACTUAL FOAM CONCENTRATES.

DO NOT USE WATER, TRAINING OR TEST FOAMS FOR FEEDBACK CALIBRA-
TION VERIFICATION.

Figure 4-8: Foam Concentrate Injection Rate Default

Value, Tank “A” Shown