Remote activation switch option – Hale FoamLogix 6.5 User Manual

Page 99

Advertising
background image

99

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual
p/n: 029-0021-68-0

Ele c tri ca l Ins ta lla tion

Use a minimum 16 AWG type SXL or GXL (SAE J1128) wire to extend the
low tank sensor wires to the 2-pin Packard WeatherPack the following con-
nectors of the main cable harness:

Tank “A” - C10

Tank “B” - C11

Low tank level sensors are not polarity sensitive therefore terminal connec-
tions are not specific.

When splicing wires make sure the splices are sealed using an adhesive
filled heat shrink tubing. Where two wires exit the heat shrink tubing pinch
the tubing while heating the it to make sure the adhesive seals around both
wires.

CAUTION !

USE THE SILICONE SEALER PROVIDED TO INSULATE AND PREVENT
CORROSION.

A connector kit (Hale p/n: 546-1780-00-0) is available that contains a Pack-
ard WeatherPack 2-contact shroud half, two (2) 14-16 gauge male terminals
and two (2) 14-16 gauge cable seals. Assemble these components to the
end of the low tank sensor wires.

Snap the two halves of the WeatherPack connector together making sure
they are sealed.

Remote Activation Switch Option

(See Figure 3-41: “Remote Activation Switch Installation Dimensions” on
page 100.)

Choose a location in the apparatus personnel compartment for mounting
the remote activation switch. Make sure the switch is accessible to the
operator without interfering with other controls on the apparatus.

Install the remote activation switch as follows:

Cutout the panel and drill the four 0.203 inch (5mm) diameter through holes.
(See Figure 3-41: “Remote Activation Switch Installation Dimensions.”)