Foam concentrate injection hose, Figure 3-20: injection and bypass hose connections, Bypass hose connection – Hale FoamLogix 6.5 User Manual

Page 72

Advertising
background image

Installer Installation

72

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual

p/n: 029-0021-68-0

Foam Concentrate Injection Hose

Connect a hose from the foam pump inject port to the inlet of the check
valve injector fitting. (See Figure 3-20: “Injection and Bypass Hose Connec-
tions.”)

Figure 3-20: Injection and Bypass Hose Connections

The hose and fittings from the INJECT port to the check valve injector fitting
should have a minimum 1/2” (13 mm) inside diameter and be rated at 500
PSI (34 BAR) working pressure (Aeroquip 2580-10 or equal).

Bypass Hose Connection

A bypass port is provided on the discharge side of the ADT, or a 1/4 turn
bypass valve is mounted on the discharge of the foam pump when the ADT
option is not installed. (See Figure 3-21: “Bypass Valve Assembly,” on page
73.)

The bypass handle must be accessible by the pump operator during normal
operations. (See Figure 3-20: “Injection and Bypass Hose Connections.”)

The bypass is a 3-way directional valve. Determine which port is the
INJECT port and which port is the BYPASS. (See Figure 3-21: “Bypass
Valve Assembly,” on page 73.)

Bypass hose connections are 1/2” (13mm). Hose fittings compatible with all
foam concentrates must be provided. The hose from the BYPASS port is
plumbed to the atmosphere and should not receive HIGH pressure.

Advertising
This manual is related to the following products: