Setup and Calibration

118

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual

p/n: 029-0021-68-0

7. Adjust the reading on the display to match the volume actually pumped using

the or button.

8. Repeat the procedure as necessary to verify the setting is correct.

9. Set the bypass valve handle back to the INJECT position.

Record Foam Feed Back Factor

1. Press and release

the

i

button.

2. The display shows

FA xxx for Tank “A”,
or FB xxx for Tank
“B” for the foam
pump feedback cali-
bration factor. (See
Figure 4-11: “Feed-
back Calibration
Factor, Tank “A”
Shown.”)

3. Record this value for

future reference on
the next page. This
factor can be programmed into the display if the display is ever replaced
or to provide a baseline calibration point.

CLASS “A” FOAM PUMP FEEDBACK

CALIBRATION FACTOR: _________________________________

CLASS “B” FOAM PUMP FEEDBACK

CALIBRATION FACTOR: _________________________________

Exit and Save Calibration

1. To exit the calibration mode and save the set values, press and hold the

i

button.

2. The display shows PASS, then clears.

3. While continuing to hold the display button enter the password (

).

Figure 4-11: Feedback Calibration Factor,

Tank “A” Shown