Se tup and Cal ibration

117

FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual
p/n: 029-0021-68-0

1. Press the

i

button.

2. The display shows A x.xx for Tank “A”, or B x.xx for Tank “B” for the total

volume of foam concentrate pumped during the last calibration run. (See
Figure 4-9: “Foam Pump Feedback Calibration, Tank “A” Shown.”)

3. Set the bypass valve to

the BYPASS position.

4. Place a graduated mea-

sure container at the out-
let of the bypass hose,
capable of containing
the expected volume of
foam concentrate, 5 gal-
lons (19 liters) minimum.
(See Figure 4-10: “Foam
Concentrate Collection”
on page 117.)

Note: If an accurate
calibrated container is
not available, use an
accurate scale to weigh the foam concentrate pumped. The total volume of foam
concentrate can then be calculated from the weight and the density of the foam
from the MSDS sheet.

5. Start the Hale FoamLogix

foam pump by pressing the
red ON button.

The LEDs on the horizontal
bar graph light as the foam
pump begins operating at
approximately two-thirds
speed, pumping foam con-
centrate into the container.
The display shows the vol-
ume of foam concentrate
being pumped.

6. STOP the foam pump and

accurately measure the
amount of foam concen-
trate collected. (See Figure
4-10: “Foam Concentrate
Collection.”)

Figure 4-9: Foam Pump Feedback Calibration,

Tank “A” Shown

Figure 4-10: Foam Concentrate Collection