2 "di2 timestamp" electronic module, 1 parameters tab, L-force controls | i/o system 1000 – Lenze L-force I/O System 1000 User Manual

Page 32

Advertising
background image

L-force Controls | I/O System 1000

Parameter setting

Electronic modules - digital input

32

L

2.0 EN - 11/2010

6.2.2

"DI2 TimeStamp" electronic module

6.2.2.1

Parameters tab
Use the Parameters tab to select the settings for the electronic module. In addition, the

channel status is indicated.

How to parameterise the electronic module:

1. Select the electronic module in the project view.
2. Click the Parameters tab in the workspace.

3. Make settings for each channel.

Legend

Description

Index

Accept module

parameter

Changed settings will not be accepted until the function has been executed.

Click the input field to open the drop down menu.

• 255: Accept module parameters

0x31FF

Channel status

Display of the current output signal.

• TRUE: Signal level = HIGH

• FALSE: Signal level = LOW

0x5430

Current channel

status ticker value

Display of the current ticker value in [μs].

0x5430

Input delay

In the case of impure input signals, signal peaks can for instance be filtered.

Click the input field to open the drop down menu.

• 00: 1 μs

• 02: 3 μs

• 04: 10 μs

• 07: 86 μs

• 09: 342 μs

• 0C: 2731 μs

DI1: 0x3102

DI2: 0x3103

Advertising