2 "do2 timestamp" electronic module, 1 parameters tab, 2 timestamp function – Lenze L-force I/O System 1000 User Manual

Page 37: L-force controls | i/o system 1000

Advertising
background image

2.0 EN - 11/2010

L

37

L-force Controls | I/O System 1000

Parameter setting

Electronic modules - digital output

6.3.2

"DO2 Timestamp" electronic module

6.3.2.1

Parameters tab
Use the Parameters tab to select the settings for the electronic module. In addition, the

channel status is indicated.

How to parameterise the electronic module:

1. Select the electronic module in the project view.
2. Click the Parameters tab in the workspace.

3. Make settings for each channel.

6.3.2.2

TimeStamp function

Description
Long cycle times or cycle times varying as a function of the fieldbus load will inevitably lead

to large inaccuracies if switching at an exact point in time is required. Using the

Legend

Description

Index

Module status

Display of the current status:

• 00h/80h: OK

• 01h/81h: No next entry

• 02h/82h: No new entries available

• 03h/83h: FIFO memory full. No new entries possible.

0x5440

Running number

Display of the "Channel status" and "Channel status ticker value" referred to

the running number (RN).

Click the input field to open the drop down menu and select the required

running number (subindex of 0x5640).

• 1 … 4

–The display values for "Channel status" and "Channel status ticker

value" are refreshed automatically.

0x5640

Channel status

Display of the current output signal.

• TRUE: Signal level = HIGH

• FALSE: Signal level = LOW

0x5640

Channel status ticker

value

Display of the current ticker value in [μs].

0x5640