L-force Controls | I/O System 1000

Error management

Monitoring

8.1.2

Heartbeat protocol

[8-1]

Heartbeat protocol

Heartbeat producer
The I/O system 1000 transmits a status telegram to the fieldbus and can thus be

monitored by other nodes.
The settings are made in index 0x1017.

Producer heartbeat is started automatically if a time > 0 is entered in index 0x1017 and

the I/O system 1000 changes to Operational.

After the cycle time has elapsed, the status telegram is transferred from the I/O

system 1000 to the fieldbus.

A reset takes place by a change to Operational.

r: reserved (always 0)

s: Status of the heartbeat producer

COB-ID = 1792 + Node-ID

Heartbeat
Consumer

Heartbeat

Producer

indication

indication

indication

indication

indication

indication

indication

indication

Heartbeat Event

request

request

Heartbeat

Producer

Time

Heartbeat

Consumer

Time

Heartbeat

Consumer

Time

0

0

1

1

r

r

s

s

7

7

6 … 0

6 … 0