2.0 EN - 11/2010

L

45

L-force Controls | I/O System 1000

Parameter setting

Electronic modules - analog output

Legend

Description

Index

Accept module

parameter

Changed settings will not be accepted until the function has been executed.

Click the input field to open the drop down menu.

• 255: Accept module parameters

0x31FF

Channel status

Display of the current output signal of 0 ... 10 V.

0x6411

Signal function

Signal function of the channel.

Click the input field to open the drop down menu.

• 16: 0...10V /0...27648dec

–Voltage signal output of 0 ... 10 V and a resolution of 0 ... 27648.

–The value range is displayed in the object.

• 32: 0...10V /0...16384dec

–Voltage signal output of 0 ... 10 V and a resolution of 0 ... 16384.

–The value range is displayed in the object.

• 255: Channel deactivated

–No output of a voltage signal

0x31xx

Error state selection

Response of the channel to an error.

Click the input field to open the drop down menu.

• Last channel status is maintained

–The voltage signal remains on the value output last.

• Channel status = status in event of error

–The voltage signal is set to the value defined in the "Error state".

0x6443

Error state

Response of the channel to an error if the "Channel status = status in event

of error" has been set in the "Error state selection".

Click the input field to open the drop down menu.

• Input of a voltage value (0 ... 10 V) that is to be output.

0x6444