Parameter setting

Save parameter settings and station structure

64

L

2.0 EN - 11/2010

6.8

Save parameter settings and station structure

6.9

Load Lenze setting

If the read-in station structure is not identical to the saved station structure after the I/O

system 1000 is switched on, the CAN bus coupler module reports an error ("SF" LED is

blinking).

Parameter | Name:

0×1010/1 | Save All Parameters
Parameter settings and station structure are saved to the EEPROM of the bus coupler.
Selection list

(Lenze setting printed in bold)

Information

0 No function

Function acc. to CANopen (communication protocol

DS301/DS401)

1702257011 Save

Parameter | Name:

0×1011/1 | Restore All Parameters
The parameter settings are reset to the Lenze setting in the EEPROM of the bus coupler.
Selection list

(Lenze setting printed in bold)

Information

0 No function

Function acc. to CANopen (communication protocol

DS301/DS401)

The Lenze setting is accepted by switching the supply

voltage off and on. All settings that have been saved

before are deleted from the EEPROM of the CAN bus

coupler.

1684107116 LOAD