L-force Controls | I/O System 1000

Parameter setting

Electronic modules - counters

Comparison value with non-zero pulse duration
The hysteresis is activated and a pulse of the parameterised duration is issued if the

comparison condition is met. As long as the count value lies within the hysteresis range, no

more pulses will be issued. When the hysteresis is activated, the counting direction is saved

to the module. If the count value exits the hysteresis range in the opposite direction of the

saved counting direction, a pulse of the parameterised duration is issued. If the hysteresis

range is exited without change of direction, no pulse will be issued.

c

Count value = comparison value: Pulse of the parameterised duration is issued, hysteresis is activated, and

the counting direction is saved

d

Hysteresis range is exited in the opposite direction of the saved counting direction: Pulse of the

parameterised duration is issued and the hysteresis is deactivated

e

Count value = comparison value: Pulse of the parameterised duration is issued, hysteresis is activated, and

the counting direction is saved

f

Hysteresis range is exited without change of direction: Hysteresis is deactivated

g

Count value = comparison value: Pulse of the parameterised duration is issued, hysteresis is activated, and

the counting direction is saved

h

Count value = comparison value and hysteresis active: No pulse

i

Hysteresis range is exited in the opposite direction of the saved counting direction: Pulse of the

parameterised duration is issued and the hysteresis is deactivated