Parameter setting

Electronic modules - digital output

Process data
Via the output area, up to 15 TimeStamp entries can be transferred to the FIFO memory.

The process image shows the status of the FIFO memory and the processing status.

See also:



PDO mapping

( 66)



PDO mapping for digital modules with TimeStamp function

( 68)

Index

Bit

Description

0x5440

0 … 5

Running number of the TimeStamp entry last written to the FIFO

memory.

6

1 (fix)

7

0 (fix)

8 … 13

Running number of the TimeStamp entry that will be processed

next.

14

1 (fix)

15

1 (fix)

16 … 23

• 00

h

or 80

h

: OK

• 01

h

or 81

h

: No next entry

• 02

h

or 82

h

: No new entries available

• 03

h

or 83

h

: FIFO memory full. No new entries possible.

–When the memory is full, there will no more TimeStamp entries

be accepted. Check the FIFO memory status before transmitting

further TimeStamp entries.

24 … 31

Number of TimeStamp entries in the FIFO memory.

Index

Bit

Description

0x5640

0 … 5

0 (fix)

6

Channel status - digital output 1 (DO1)

• 0: FALSE

• 1: TRUE

7

Channel status - digital output 2 (DO2)

• 0: FALSE

• 1: TRUE

8 … 15

Running number (RN)

16 … 31

Ticker value