L-force Controls | I/O System 1000

Networking via CAN system bus

Port assignment

The following rules for assigning the PDOs apply according to the CANopen

communication profile DS401:

PDO

Assignment

RPDO1

Reserved for the first digital input module.

TPDO1

Reserved for the first digital output module.

RPDO2

Reserved for the first analog input module.

TPDO2

Reserved for the first analog output module.

FROM PDO3

The PDOs can only be assigned with electronic modules of one module class. Free bytes are

reserved for modules of the same module class.

• Sort order of the module classes:

–Digital modules

–Analog modules

–Counter modules

–SSI module

–PWM module

–Digital output modules TimeStamp

–Digital input modules TimeStamp

Note!

In order to ensure data consistency, the data in the PDOs are mapped as follows:
• Digital input module / Digital output module:

– With digital values, an electronic module is always mapped in one byte. If

the byte in a PDO has not enough free bits, the electronic module is

mapped in the next byte.

• Analog input module / Analog output module:

– With analog values the data lengths of which exceed on byte, the data

consistency is extended. Since one channel assigns two bytes, each channel

of an electronic module is mapped in two successive PDOs.