2 control of the counter, L-force controls | i/o system 1000 – Lenze L-force I/O System 1000 User Manual

Page 49

Advertising
background image

2.0 EN - 11/2010

L

49

L-force Controls | I/O System 1000

Parameter setting

Electronic modules - counters

6.6.2

Control of the counter

The counter is controlled via the hardware gate (HW gate) and the software gate (SW gate).

The HW gate and the SW gate are combined with an AND operation.

The HW gate is controlled via the signal at input 8 of the counter module.

Gate function

Signal - SW gate

Signal - HW gate

Counter response

Cancel

0

0-1 edge

Counting process stops

0-1 edge

0

1

0-1 edge

Starts counting process

with start value

0-1 edge

Deactivated

0-1 edge

1

Continues counting

process with the current

counter content

Pause

0

0-1 edge

Counting process stops

0-1 edge

0

1

0-1 edge

Continues counting

process with the current

counter content

0-1 edge

Deactivated

0-1 edge

1

Note!

• In the "Counting only once" mode, the control of the counter is restricted.

– For a restart after a complete counting process, the counter requires

corresponding start signals via the HW gate and the SW gate.

A start signal via the SW gate will not cause the counting process to start if

the HW gate is deactivated.

• The SW gate is addressed via bit 2 of the control word (0x5602/x):

– In the »Engineer«, bit 2 can be controlled directly in index 0x5602/x in the

object list.

– Control via PDO (see PDO mapping in the I/O system 1000 system manual).