Figure 6.7
System Grounding Procedures

Power Stage

Interface Board

Control

Boards

Unit

Power

Supply

GND

Control (Signal)
Common

TE

GND

TE

Power Stage

Interface Board

Control

Boards

Unit

Power

Supply

Control (Signal)
Common

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

System TE Bus

System PE Bus

TB

1

TB

2

TB

1

TB

2

1395 Drive

1395 Drive

1–30 HP 230VAC
2–60 HP 460VAC

40–100 HP 230VAC
75–200 HP 460VAC

125–300 HP 230VAC
250–600 HP 460VAC

TB

1

TB 4

TB 4

TB 10

Terminals 4 & 5, TB2

TB

2

Terminals 6 & 7, TB2

Terminals 10 & 11, TB5

TE

PE

PE

PE

On a multi drive system, assure that the TE bus of each drive is directly
connected to the system TE bus. In addition, the Safety Ground (PE) of
each drive must be directly connected to the system PE bus.

IMPORTANT: PE must be connected in a “star” fashion and not daisy
chained.