Chapter 4

Hardware Description
125 - 300 HP, 230VAC 250 - 600 HP, 460VAC

4-14

Power Distribution

115VAC Control Voltage - Figure 4.11 illustrates the distribution of
115VAC control voltage within the Bulletin 1395. Single phase 115VAC

control voltage, provided from an external source by the user enters the

drive at TB5-4 and 5. Fuse F4 provides protection against short circuits on

the 115VAC input to the drive terminal block TB6 (an internal terminal

block).

Figure 4.11
115VAC Control Voltage Distribution

1
2
3
4
5
6
7
8
9

10

TB5

115 VAC

TE

PE

To Relay Logic

1
2
3
4
5
6
7
8
9

TB6

F4

10

11

12

13

14

15

16

17
18

See

Fig.

4.2

F5

H1

X1

115

VAC

20

VAC

X2

H2

PT

SPMOV

6

5

A7

Power Stage Interface

1 2

A6

Unit Power Supply

3

NOTE: To provide DC Contactor

energization, a jumper or other ex-

ternal circuitry must be connected

to TB5-8 and 9.

2

3

TB9

Fan

1

Fan

2

Fan

3

11

12

M1

PR

J1

1

4

See

Fig.

4.12

D1

1.5 AMP

7 AMP

L1

L2

PE

See Fig

4.13

See Fig

4.12

L3

Common