Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual
Page 155
Chapter 6
Installation
6-31
24VDC Connection/Digital Input – Sizing of the power supply is based
on the number of input and output selections. Figure 6.18 shows the
typical connection of the digital input using the external power supply.
Analog Input – Velocity and Trim Reference. Connections for the
velocity and trim reference inputs can be for uni- or bi-directional
operation, using the internal drive
±
10VDC power supply (see Fig.6.19 ).
Figure 6.18
Typical 24VDC Digital Input Connections using External Power Supply
DIGITAL IN 2
47
48
49
50
51
TB3
DIGITAL COMMON
DIGITAL IN 1
DIGITAL IN 3
DIGITAL IN 4
Clear Faults*
Start*
Jog 2*
Stop*
24V DC Common
24V DC High
* External to the Drive
Figure 6.19
Typical Analog Input Connections
32
31
+
–
33
TB3
+10V DC P.S.
–10V DC P.S.
ANALOG INPUT
P.S. COMMON
Bi-directional Operation
IMPORTANT: Connect
shield to drive end only.
Other end is to be insu-
lated and left floating.
Reference*
2.5k Ohm
Minimum
32
31
+
–
33
TB3
+10V DC P.S.
–10V DC P.S.
ANALOG INPUT
P.S. COMMON
TB4 (TB-10 on 125-600 HP)
Uni-directional Operation
IMPORTANT: Connect
to either terminal 31 or
32, Not Both
Reference*
2.5k Ohm
Minimum
R
R
Forward
Reverse
R*
Reverse Relay
* External to the Drive
*
TB4 (TB-10 on 125-600 HP)