Chapter 6
Installation

6-18

ATTENTION: The motor field supply is phase sensitive. To
guard against possible drive/motor damage, ensure that the
connections are properly made according to Figure 6.8, 6.9, 6.11
and 6.12.

!

Figure 6.11
External Field Transformer Connections

TB1

2

3

4

5

TB1

1

40 –100 HP, 230VAC
75 – 200 HP, 460VAC

125-300 HP, 230VAC
250-600 HP, 460VAC

TB8

to Field Bridge

L1

L3

1

3

L1

L3

2

3

4

Field Transformer
Secondary
460V

1-30HP, 230VAC
2-60 HP, 460VAC

1. The primary of the external field transformer requires branch circuit protection, to be fused with FRN or FRS style fuses. Refer to NEC Code (and local codes) for

sizing.

2. As noted, the secondary of the external field transformer must be fused with semi conductor type fuses; type FWH-25 or FWH-50 depending on Drive HP rating.

230V

Field Transformer
Secondary
460V

230V

Sized to load

230V

Field Transformer
Secondary

50A

50A

25A

25A

FU

FU

L1

L3

FU

FU

1

1

1

FU

FU

1

1

460V

MKVA Series B

Series A

Series B

Circuit Board Jumper Connections

There are several jumpers located on different boards in the 1395 that are
used to configure the drive for a specific application.

1. Verify that the motor field current jumper is in the proper location per

Table 6.H. Obtain the motor full field current data from the motor
nameplate. The position of the jumper is determined by both the drive
current rating and DC shunt field current rating. Use the drive current
rating to select the column in Table 6.H and the field current to select
the field current jumper position.